Generator Relay Model: LHSRT

 

The values of dstrp1, dstrp2, … dstrp10 represent deviations from synchronous speed in per unitThe test for determining whether the relay will trip is as follows.

Value = generator speed deviation from synchronous speed in per unit

If (dstrp1 > 0) and (Value > dstrp1) then activate timer for dttrp1 else Reset the timer

If (dstrp1 < 0) and (Value < dstrp1) then activate timer for dttrp1 else Reset the timer

 

Each timer acts independently of other timers. If a time remains active for longer than the respective dttrpX value, then it will trip the generator.

 

Parameters:

dstrp1 Delta speed trip level, pu
dstrp2 Delta speed trip level, pu
dstrp3 Delta speed trip level, pu
dstrp4 Delta speed trip level, pu
dstrp5 Delta speed trip level, pu
dstrp6 Delta speed trip level, pu
dstrp7 Delta speed trip level, pu
dstrp8 Delta speed trip level, pu
dstrp9 Delta speed trip level, pu
dstrp10 Delta speed trip level, pu
dttrp1 Speed trip time, sec.
dttrp2 Speed trip time, sec.
dttrp3 Speed trip time, sec.
dttrp4 Speed trip time, sec.
dttrp5 Speed trip time, sec.
dttrp6 Speed trip time, sec.
dttrp7 Speed trip time, sec.
dttrp8 Speed trip time, sec.
dttrp9 Speed trip time, sec.
dttrp10 Speed trip time, sec.
Alarm If greater than zero, no tripping action is enforced; a message is printed when a trip level is exceeded.

Model supported by PSLF